معرفی محصول
رله بریر مدل MTL4516-5516c دارای دو کانال و قابلیت تشخیص خط خطاو فاز نرمال است .این رله در مناطق ضد
انفجار استفاده میشود.
Outputs closed if input > 2.1mA (< 2kΩ in input circuit
Outputs open if input < 1.2mA (> 10kΩ in input circuit
توضیحات محصول
The MTL4516-5516c enable two safe-area loads to be controlled by a switch or proximity detector located in a hazardous-area. When
selected, open or short circuit conditions in the field wiring are detected by the linefault-detect (LFD) facility and also indicated on the
top of the module. Phase reversal for each channel is selected by a switch on the side of the module and output is provided by
changeover relay contacts
Number of channels Two
Location of switches Zone 0, IIC, T6 hazardous area Div. 1, Group A hazardous location
Location of proximity detector Zone 0, IIC, T4–6 hazardous area if suitably certified Div. 1, Group A hazardous location Hazardous-area
inputs Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)
Voltage applied to sensor 7 to 9V dc from 1kΩ ±10%
Input/output characteristics Normal phase Outputs closed if input > 2.1mA (< 2kΩ in input circuit) Outputs open if input < 1.2mA (>
10kΩ in input circuit) Hysteresis: 200µA (650Ω) nomina
Safe-area output Two single-pole relays with changeover contacts
Note: reactive loads must be adequately suppressed
SIL capable
These models have been assessed for use in IEC 61508 functional safety applications. SIL2 capable for a single device (HFT=0) SIL3
capable for multiple devices in safety redundant configurations (HFT=1) See data on MTL web site and refer to the safety manual